Energy And Power Products
Distribution Transformer
Electropac Limited produces Distribution Transformers up to 5MVA. It is one of the primary items of the company. Distribution Transformers derives its name from its usage in the electricity grid where its function is to step down the electrical voltage in the distribution line to a level that can be used by electricity consumers. We follow our own design and construction features to manufacture distribution transformers besides the international standards. Our transformer has TYPE TEST certificate from CPRI, India. Our overall objective in the production house is to meet client objective and customize it according to the requirements in the electrical system.

SL. No | Capacity (KVA) | Voltage (KV) | Vector Group | % lmp | Losses (Watt) | % Regulation At Unity Power Factor | % Eflciency At Unity Power Factor | Out the Dimension Approx. (mm) | Oil Weight (Litter) | Total Weight (KG) | |||
No Load | Load at 750 C | At Full Load | At Full Load | L | W | H | |||||||
1 | 50 | 11/0.415 | DYn 11 | 4% | 150 | 925 | 1.72 | 98.25 | 760 | 330 | 750 | 150 | 650 |
2 | 100 | 11/0.415 | DYn 11 | 4% | 245 | 1695 | 1.61 | 98.57 | 780 | 350 | 780 | 200 | 750 |
3 | 150 | 11/0.415 | DYn 11 | 4% | 315 | 2100 | 1.36 | 98.61 | 830 | 370 | 820 | 250 | 870 |
4 | 200 | 11/0.415 | DYn 11 | 4% | 425 | 2800 | 1.25 | 99.67 | 870 | 390 | 920 | 300 | 1020 |
5 | 250 | 11/0.415 | DYn 11 | 4% | 510 | 3180 | 1.22 | 98.72 | 940 | 420 | 960 | 390 | 1210 |
6 | 315 | 11/0.415 | DYn 11 | 4% | 540 | 3700 | 1.19 | 98.79 | 980 | 440 | 990 | 420 | 1310 |
7 | 400 | 11/0.415 | DYn 11 | 5% | 650 | 5010 | 1.12 | 98.83 | 1060 | 450 | 1050 | 500 | 1520 |
8 | 500 | 11/0.415 | DYn 11 | 5% | 850 | 5600 | 1.08 | 98.91 | 1140 | 500 | 1110 | 600 | 1820 |
9 | 630 | 11/0.415 | DYn 11 | 6% | 900 | 6100 | 1.06 | 98.99 | 1190 | 520 | 1160 | 700 | 2050 |
10 | 750 | 11/0.415 | DYn 11 | 6% | 1100 | 8100 | 0.99 | 99.05 | 1240 | 540 | 1220 | 800 | 2440 |
11 | 800 | 11/0.415 | DYn 11 | 6% | 1150 | 8300 | 0.97 | 99.07 | 1250 | 550 | 1320 | 880 | 2650 |
12 | 1000 | 11/0.415 | DYn 11 | 6% | 1450 | 9500 | 0.92 | 99.13 | 1330 | 570 | 1400 | 1020 | 3010 |
13 | 1250 | 11/0.415 | DYn 11 | 6% | 1650 | 11500 | 0.87 | 99.15 | 1360 | 600 | 1420 | 1250 | 3530 |
14 | 1500 | 11/0.415 | DYn 11 | 7% | 2000 | 13010 | 0.85 | 99.16 | 1480 | 610 | 1524 | 1480 | 4420 |
15 | 1600 | 11/0.415 | DYn 11 | 7% | 2200 | 14000 | 0.85 | 99.17 | 1540 | 620 | 1560 | 1580 | 4810 |
16 | 2000 | 11/0.415 | DYn 11 | 7% | 2500 | 15000 | 0.83 | 99.19 | 1590 | 680 | 1680 | 1900 | 5810 |
17 | 2500 | 11/0.415 | DYn 11 | 7% | 2650 | 18000 | 0.81 | 99.23 | 1720 | 740 | 1680 | 2100 | 6050 |
18 | 3000 | 11/0.415 | DYn 11 | 7% | 3000 | 20000 | 0.89 | 99.28 | 1740 | 760 | 1880 | 2500 | 6600 |
1 | 3 phase | 11/0.415 KV | 50 Hz | 50 KVA |
2 | 3 phase | 11/0.415 KV | 50 Hz | 100 KVA |
3 | 3 phase | 11/0.415 KV | 50 Hz | 150 KVA |
4 | 3 phase | 11/0.415 KV | 50 Hz | 200 KVA |
5 | 3 phase | 11/0.415 KV | 50 Hz | 250 KVA |
6 | 3 phase | 11/0.415 KV | 50 Hz | 315 KVA |
7 | 3 phase | 11/0.415 KV | 50 Hz | 400 KVA |
8 | 3 phase | 11/0.415 KV | 50 Hz | 500 KVA |
9 | 3 phase | 11/0.415 KV | 50 Hz | 630 KVA |
10 | 3 phase | 11/0.415 KV | 50 Hz | 750 KVA |
11 | 3 phase | 11/0.415 KV | 50 Hz | 1000 KVA |
12 | 3 phase | 11/0.415 KV | 50 Hz | 1250 KVA |
13 | 3 phase | 11/0.415 KV | 50 Hz | 1500 KVA |
14 | 3 phase | 11/0.415 KV | 50 Hz | 1600 KVA |
15 | 3 phase | 11/0.415 KV | 50 Hz | 2000 KVA |
16 | 3 phase | 11/0.415 KV | 50 Hz | 2500 KVA |
17 | 3 phase | 11/0.415 KV | 50 Hz | 3000 KVA |
HT Switchgear
Electropac High Tension Switchgear comprises the units designed for rated voltage of 11KV and current range upto 1250A. The switchgear comprises of SF6 Circuit Breaker, Vacuum Circuit Breaker, Load Break Switch, Vacuum Contactor, Disconnector etc.
CONSTRUCTION | Sheet Steel, Metal clad |
RATED VOLTAGE | 11KV |
RATED CURRENT | 630A, 1250A |
RATED FREQUENCY | 50HZ |
Short Time Current Ratings for 3 Seconds : 20KA, 31.5KA

LT Switchgear
Electropac Low Tension Switchgear equipped with sheet steel, metal clad, dust and vermin proof, free standing, foor mounting type, 415V, 50Hz upto 5000A, indoor type low Tension Switchgear and Synchronizing panel to control & distribute the power in different installations like Power Stations, Industries, Mills & Factories, Housing & Commercial complex & other important Installations.
CONSTRUCTION | Metal clad |
RATED VOLTAGE | Upto 1000V |
RATED CURRENT | Upto 5000A |
RATED FREQUENCY | 50Hz |
Short Time Current Ratings for 1 Seconds : 50KA

Power Factor Improvement Plant (PFI)
Electropac Power Factor Improvement Plant has been designed to meet the needs of all forms of power factor correction by Capacitor Banks from small unit to a large Plant. Electorpac PFI plants are preferable designed to eliminate the penalties for consumption of reactive prower, reduction of voltage drop, increase in transformer capacity with same losses (load), reduction of line losses.
CONSTRUCTION | Sheet Steel, Metal Clad |
RATED VOLTAGE | 415V |
CAPACITY | Upto 3000 KVAR |
RATED FREQUENCY | 50Hz |

Generator Synchronizing Panel
Our Generator Synchronization Panels are assembled and designed by Electropac. This can be built by the recommendation of our engineers or customized by customers requirements. Our panels are capable or producing up to 10000A and build with high quality materials, electrical components, breakers, transformers, etc.